SF6 Infrared Sensor - WFS-S1-S

? Infrared spectral absorption principle (NDIR).
? Dual wavelength, with temperature compensation.
? High reliability, no cross reaction with other gases.
? Compared with electrochemical sensors, SF6 sensor infrared sensors have a lifetime of up to 10 years.
? Cost-effective, affordable discounted prices.

  • Model Number: WFS-S1-S
Quantity:
- +
  • SF6 Infrared Sensor
Mouse over image to zoom
Share:

Product Specification

SF6 Infrared SensorWFS-S1-SOverview

    SF6 Infrared Sensor (S1-GP-S) is based on dual-beam dual-wavelength infrared measurement technology and high-precision digital processing technology. It is widely used in high pressure switch GIS room SF6 gas leakage monitoring (0-100ppm), SF6 gas leak detector (0- 50ppm) and SF6 Purity Analyzer (0-100%). Internal integrated complete drift automatic control and temperature compensation circuit.

 

    SF6 infrared sensor (S1-GP-S) adopts dual-beam non-spectral infrared (NDIR) detection technology, which has anti-interference with other gases, easy maintenance, good stability, and built-in temperature compensation. Standard Modbus ASCII protocol, digital output and analog output optional. Suitable for SF6 leak alarm, on-site construction protection, single gas precision analysis, online monitoring, industrial process analysis and many other applications.

 

SF6 Infrared SensorWFS-S1-SFeatures

    The unique light-free tank NDIR technology is adopted, equipped with a high-breathable stainless steel housing, and an external oxygen sensor can be used for digital signal output. Due to the design of specific wavelengths for SF6, it is resistant to other gases, does not require air pump piping, small size, solid and corrosion resistant housing, easy to use and maintain, adapt to harsh environments, and can simultaneously upload and output sulfur hexafluoride content and oxygen content, etc. Suitable for leak alarm, environmental testing, on-line monitoring, gas composition analysis and other applications.

 

The advantages of infrared SF6 sensors compared to electrochemical and negative corona discharge principles:

? Infrared spectral absorption principle (NDIR).

? Dual wavelength, with temperature compensation.

? High reliability, no cross reaction with other gases.

? Compared with electrochemical sensors, SF6 sensor infrared sensors have a lifetime of up to 10 years.

? Cost-effective, affordable discounted prices.

? Compared with electrochemical sensors, SF6 sensor eliminates after-sales maintenance costs.

? Digital and analog output modes are optional, and secondary development and application are convenient.

? Micro structure, low power design.

? No radiation source, no secondary hazards.

 

The infrared SF6 purity sensor (0-100% Vol.) offers significant advantages over the principle of thermal conductivity:

? The infrared SF6 purity sensor is small in size.

? Infrared SF6 purity sensor with low power consumption, battery-powered.

? The infrared SF6 purity sensor does not require a large heating system.

? The infrared SF6 purity sensor has a wide operating temperature (-20-+60).

? Over 5.3 years of calibration cycle, there is no need to check the instrument frequently.

? High reliability and stability, no need to maintain the SF6 purity analyzer daily.

 

SF6 Infrared SensorWFS-S1-STechnical Parameters

Gas detection

Sulfur hexafluoride (SF6)

Detection principle

non-dispersive infrared absorption detection (NDIR)

Detection range

0 ~ 2000ppm (standard type), other ranges can be customized

Detection accuracy

≤±2% FS 1

Working temperature

-15 to 45 degrees Celsius

Working pressure

950 to 1050 mb

Environmental humidity

0 to 95% RH

Warm-up time

less than 2 minutes

Response time

approximately 30 seconds (Td90, measured at 50% FS)

Operating voltage

5V

Operating current

less than 200 mA

Output signal

UART, other forms can be customized

Auxiliary function

Take one ADC and connect the oxygen sensor

Service life

more than 6 years

Storage temperature

-25 to 55 degrees Celsius

Discrimination

1 ppm

Repeatability

≤±2% FS 1

Linearity error

≤±1% FS 1

Lower detection limit

<10 ppm


If you cannot find what you want, you can entrust ISweek to source for you. Just click:

Sourcing Service
国产精品麻豆欧美日韩WW| 无码人妻一区二区三区精品视频| 精品精品国产国产| 精品久久久久久久久亚洲偷窥女厕 | 久久婷婷国产综合精品| 国产99久久亚洲综合精品| 日韩精品人妻系列无码专区| 精品99在线观看| 97精品人妻系列无码人妻| 国产999精品2卡3卡4卡| 国产成人精品无缓存在线播放| 亚洲男人的天堂久久精品| 国产精品亲子乱子伦xxxx裸| 日韩视频中文字幕精品偷拍 | 午夜精品一区二区三区在线观看| 国产麻豆精品原创| 人妻少妇精品中文字幕AV| 国产亚洲精品看片在线观看| 国产在线精品无码二区二区| 国内精品自线在拍2020不卡| 久久精品a亚洲国产v高清不卡| 亚洲午夜国产精品无码老牛影视 | 国产亚洲精品观看91在线| 午夜一级日韩精品制服诱惑我们这边 | 国产精品高清视亚洲一区二区| 久久99精品国产免费观看| 水蜜桃精品一二三| 精品国产污污免费网站入口在线| 国产精品公开免费视频| 欧美精品久久天天躁| 国产精品久久女同磨豆腐| 日韩精品真人荷官无码| 国内精品免费在线观看| 国产成人精品亚洲精品| 国产精品妇女一二三区| 国内精品自产拍在线观看| 国产1024精品视频专区免费| 99热在线精品免费播放6| 日本精品久久久中文字幕| 久久亚洲国产精品五月天婷| 精品大臿蕉视频在线观看|